Emergency/exit light testing tasks and procedures

Body

Monthly 5 minute discharge test of emergency/exit lighting system by shutting off normal power to battery backup or inverters 

For buildings S,G & Q [ Monthly test of emergency/exit lighting system including 30 minute transfer switch and generator operation with a post run inspection of generator]

January PMs should be 90 minute testing instead of 5 minutes or 30 minutes